Bộ lập trình nhúng IoT Wise và lưu trữ Datalogger ICP DAS WISE-5801

Thương hiệu: ICP DAS | Tình trạng: Còn hàng
Liên hệ

WISE-5801 CR User-defined I/O & Data Logger Module with SMS Function for Modbus RTU or DCON Devices

Gọi 0904251826 để được trợ giúp

Bộ lập trình nhúng IoT Wise và lưu trữ Datalogger ICP DAS WISE-5801

WISE-5801: User-defined I/O & Data Logger Module with SMS Function for Modbus RTU or DCON Devices

Introduction

WISE (Web Inside, Smart Engine) is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications. WISE offers a user-friendly and intuitive web site interface that allows users to implement IF-THEN-ELSE control logic on controllers just a few clicks away; no programming is required. With its powerful and easy-to-use features, it will minimize the learning curve, shorten time to market and dramatically reduce the effort and cost spent on system development.

WISE-5801 supports an I/O expansion bus to implement various I/O functions such as D/I, D/O, A/D and D/A according to the XW-Board. In addition, it also support ICP DAS I-7000 / M-7000 remote I/O modules and Modbus RTU slave devices. Based on the variety I/O module of I-7000 / M-7000 and the connection ability with Modbus RTU slave devices, WISE-5801 can provide user more flexibility in application field.

WISE-5801 supports Modbus TCP/RTU protocol to make seamless integration with SCADA software available. It include all advantages which WISE series controllers can provide. In addition, WISE-5801 provide data logger function with microSD card, it can record I/O channel value by event trigger or regular time period. The data files can be sent back by Email or FTP. All setting can be completed through browser.

In addition to merits inherited from the existing WISE series, WISE-5801 even provides more supports in I/O functions. It allows to connecting with a wide range of XW-Boards, I-7000 / M-7000 Remote I/O modules and Modbus RTU slave devices that enables users to freely choose the most suitable I/O modules. With the microSD card, it provides Data Logger function to real-time record the I/O data of the controller and send the data files by FTP or Email at a scheduled time to the control center for further administration management or data analysis. WISE-5801 also features SMS sending function for alarm report and SMS command receiving function.

Features

  • Built-in Web Server for IF-THEN-ELSE rule setting

  • Built-in IF-THEN-ELSE rule enigne for logic operation

  • Support IO, Counter, Timer, Schedule, Email, Recipe operations

  • No more programming. Just click and get done!

  • Data logger and data files send back function supported

  • Modbus TCP/RTU Protocol for SCADA Software Seamless

  • 10/100 Base-TX Ethernet

  • Support XW-Board

  • Support I-7000 Remote I/O Modules (Up to 16)

  • Support Modbus RTU Slave Devices (Up to 10)

  • SNTP Time Synchronization Supported

  • Support SMS (GSM: Quad-band 850/900/1800/1900 MHz)

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote diagnosis and Testing Equipment, etc.

Hardware Specifications

CPU Module

CPU

16-bit CPU

SRAM

768 KB

Flash

512 KB

microSD Expansion

Support up to 32 GB microSDHC card

RTC (Real Time Clock)

RTC Provide seconds, minutes, hours, date of week/month; month and year

Watchdog Timers

Yes (0.8 second)

Communication Ports

Ethernet

RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, Auto MDI/MDI-X, LED indicators)

COM 1

RS-232 (TxD, RxD, RTS, CTS, GND), non-isolated, Speed: 115200 bps max.

COM 2

RS-485 (D2+, D2-), self-tuner ASIC inside, non-isolated, Speed : 115200 bps max.

LED Indicators

System LED

Yes (Red)

Ethernet Link LED

Yes (Green : Ethernet link detected, Flashing Green : Ethernet packet received)

Hardware Expansion

I/O Expansion Bus

Yes

SMS Function

Frequency Band

Quad-band 850/900/1800/1900 MHz

Mode

Text and Unicode mode

Power Requirements

Protection

Power Reverse Polarity Protection

Frame Ground

Yes (for ESD Protection)

Input Range

12 ~ 48 VDC

Redundant Power Input

Yes

Power Consumption

2.0 W

Mechanical

Dimensions (W x H x D)

91 mm x 132 mm x 52 mm

Installation

DIN-Rail

Environment

Operating Temperature

-25 ~ +75 °C

Storage Temperature

-30 ~ +80 °C

Ambient Relative Humidity

10 ~ 90% RH (non-condensing)

Software Specifications

Functions

Rule Configuration Website

Access Web server on WISE controllers to edit and upload logic rules through web browser.

36 IF-THEN-ELSE Logic Rules

3 IF conditions with AND or OR operators
3 THEN actions and 3 ELSE actions

48 Internal Registers

Hold temporary variables and read/write data via Modbus/TCP address.

12 Timers

Delay / Timing functions.

12 Schedules

Setup prescheduled routine tasks.

12 Emails

Send Email messages to pre-set Email receivers.

12 SMS

Send SMS to pre-set mobile phone numbers.

12 CGI Commands

Send pre-set CGI commands.

12 Recipes

Set up THEN/ELSE action groups.

Data Logger

Set up the Data Logger configuration, include the data record format, and data file sending operation.

Modbus TCP/RTU Protocol

Real time control and monitoring I/O channels and system status of controllers via SCADA software.

IF Conditions

DI Channel

ON、OFF、ON to OFF、OFF to ON、Change

AI Channel

= 、> 、< 、 ≥ 、 ≤ (value)

Internal Register

DI Counter

= 、> 、< 、 ≥ 、 ≤ (value)、Change

Timer

Timeout、Not Timeout

Schedule

In Range、Out of Range

SMS Command

0、1

Rule Status

Enable、Disable

THEN / ELSE Actions

DO Channel

ON、OFF、Pulse Output (apply to XW-Board only)

AO Channel

Change the value

Internal Register

DI Counter

Reset

Timer

Start、Reset

Schedule

Enable、Disable

Email

Send

SMS Alarm

CGI Commands

Recipe

Execute

Data Logger

Start、Stop、One-Time Log

Rule Status

Enable、Disable

Support I/O Module List

I/O Type

Functions

Modules

I-7000 Remote I/O Module

AI/AO

Voltage & Current

I-7012, I-7012D, I-7012F, I-7012FD, I-7017, I-7017F, 
I-7017R, I-7017C, I-7017FC, I-7017RC, I-7017R-A5, 
I-7017Z

Thermocouple

I-7011, I-7011D, I-7011P, I-7011PD, I-7018, I-7018BL, 
I-7018P, I-7018R, I-7018Z, I-7019R

RTD

I-7013, I-7013D, I-7015, I-7015P, I-7033, I-7033D

Thermistor

I-7005

Transmitter

I-7014D

Strain Gauge

I-7016 I-7016D I-7016P I-7016PD

Analog Output

I-7021, I-7021P, I-7022, I-7024, I-7024R

DI/DO

DC Digital Input

I-7041, I-7041D, I-7041P, I-7041PD, I-7051, I-7051D, 
I-7052, I-7052D, I-7053_FG, I-7053D_FG

AC Digital Input

I-7058, I-7058D, I-7059, I-7059D

DC Digital Output

I-7042, I-7042D, I-7043, I-7043D, I-7045, I-7045D, 
I-7045-NPN, I-7045D-NPN

DC Digital Input & Output

I-7044, I-7044D, I-7050, I-7050D, I-7050A, I-7050AD, 
I-7055, I-7055D, I-7055-NPN, I-7055D-NPN

Relay Output

Power Relay Output

I-7060, I-7060D, I-7061, I-7061D, I-7063, I-7063D, 
I-7065, I-7065D, I-7067, I-7067D

Solid State Relay Output

I-7063A, I-7063AD, I-7063B, I-7063BD, I-7065A, 
I-7065AD, I-7065B, I-7065BD

Photomos Relay Output

I-7066, I-7066D

Others

Counter/Frequency

I-7080, I-7080D, I-7080B, I-7080BD, I-7088

DL Series

Temperature and Humidity

DL-100T485, DL-100T485-W

CO2 / Temperature / Humidity

DL-302

XW-Board

DI/DO

XW107, XW110

DI/DO/AI/AO

XW304, XW310, XW310C

M-7000 / Modbus RTU Slave Module

Coil Output / Discrete Input / Input Register / Holding Register

Download

Manual

Software

Data sheet

Certification

Odering information

WISE-5801 CR User-defined I/O & Data Logger Module with SMS Function for Modbus RTU or DCON Devices

Accessories

  • GPSU06U-6 : 24 V/0.25 A, 6 W Power Supply

  • MDR-20-24 : 24 V/1 A, 24 W Power Supply with DIN-Rail Mounting

  • NS-205 CR : Unmanaged 5-Port Industrial Ethernet Switch (RoHS)

  • NS-205PSE CR : Unmanaged 5-Port Industrial PoE Ethernet Switch (RoHS)

Sản phẩm đã được thêm vào giỏ hàng