Tổng tiền thanh toán:
-
Sản phẩm đã được thêm vào giỏ hàng
Số lượng:
Tổng tiền:
M-7011-G CR 1-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS)
Module 1 kênh đầu vào cặp nhiệt + 1 kênh đầu vào số + 2 kênh đầu ra số kết nối RS-485 Modbus RTU ICP DAS M-7011
Features
1-channel Analog Input
Current, Voltage or Thermocouple Input
Open Thermocouple Detection
High Resolution: 16-bit
1-channel Digital Input as 50 Hz Event Counter
1-channel Digital Output as High/Low Alarm
3000 VDC Intra-module Isolation
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
Introduction
The I-7011 series of modules feature current and voltage input, as well as thermocouple input. The module provides 1-channel Analog Input, 1-channel Digital Input that functions as a 50 Hz event counter, and 2-channel Digital Output that can be used as a high/low alarm. The module also features open wire detection for the thermocouple input, and 3000 VDC intra-module isolation. The M-7011 supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7011. The I-7011P provides support for two additional thermocouple types, L and M.
Application
Building Automation
Factory Automation
Machine Automation
Remote Maintenance
Remote Diagnosis
Testing Equipment
I/O Specification
Models |
I-7011 |
I-7011P |
M-7011 |
|
I-7011D |
I-7011PD |
M-7011D |
||
Analog Input |
||||
Channels |
1 |
|||
Wiring |
Differential |
|||
Sensor Types |
Thermocouple |
J, K, T, E, R, S, B, N, C |
J, K, T, E, R, S, B, N, C, L, M |
J, K, T, E, R, S, B, N, C |
Voltage |
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V |
|||
Current |
±20 mA (requires optional external 125 Ω resistor) |
|||
Resolution |
16-bit |
|||
Accuracy |
0.1% of FSR |
|||
Sampling Rate |
10 Hz (Total) |
|||
Input Impedance |
> 400 kΩ |
|||
Common Voltage Protection |
±5 VDC |
|||
Individual Channel Configuration |
- |
|||
Overvoltage Protection |
±5 VDC |
|||
Open Wire Detection |
Yes |
|||
Temperature Output Consistency |
- |
|||
Stable Temperature Output in the Field |
- |
|||
Digital Input |
||||
Channels |
1 |
|||
Contact |
Dry |
|||
Sink/Source (NPN/PNP) |
Source |
|||
ON Voltage Level |
Close to GND |
|||
OFF Voltage Level |
Open |
|||
Counter |
Yes |
|||
Input Impedance |
3 kΩ |
|||
Overvoltage Protection |
±30 VDC |
|||
Digital Output |
||||
Channels |
2 |
|||
Type |
Open Collector |
|||
Sink/Source (NPN/PNP) |
Sink |
|||
Load Voltage |
+3.5 ~ +30 VDC |
|||
Max. Load Current |
30 mA/Channel |
|||
Power-on Value |
Yes |
|||
Safe Value |
Yes |
System specification
Models |
I-7011 |
I-7011P |
M-7011 |
I-7011D |
I-7011PD |
M-7011D |
|
Communication |
|||
Interface |
RS-485 |
||
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
||
Format |
N, 8, 1 |
||
Baud Rate |
1200 to 115200 bps |
||
Protocol |
DCON |
Modbus RTU, DCON |
|
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
||
LED Indicator/Display |
|||
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
||
I/O LED Indicator |
- |
||
7-Segment LED Display |
- |
||
Yes |
|||
Isolation |
|||
Intra-Module Isolation, Field-to-Logic |
3000 VDC |
||
EMS Protection |
|||
ESD (IEC 61000-4-2) |
±2 kV Contact for each Terminal |
||
EFT (IEC 61000-4-4) |
±4 kV to Power Line |
||
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
||
Power |
|||
Reverse Polarity Protection |
Yes |
||
Input Range |
+10 ~ +30 VDC |
||
Consumption |
0.9 W |
||
1.5 W |
|||
Mechanical |
|||
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
||
Installation |
DIN-Rail or Wall Mounting |
||
Environment |
|||
Operating Temperature |
-25 to +75°C |
||
Storage Temperature |
-40 to +85°C |
||
Humidity |
10 to 95% RH, Non-condensing |
Download
Odering information
I-7011 CR |
1-channel Thermocouple Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7011D CR |
I-7011 with with 7-segment LED Display (Blue Cover) (RoHS) |
I-7011P CR |
1-channel Thermocouple Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7011PD CR |
I-7011P with 7-segment LED Display (Blue Cover) (RoHS) |
M-7011-G CR |
1-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |
M-7011D-G CR |
M-7011 with 7-segment LED Display (Gray Cover) (RoHS) |
Số lượng: