Bộ chuyển đổi CANopen sang Modbus RTU ICP DAS I-7232D

Thương hiệu: ICP DAS | Tình trạng: Còn hàng
Liên hệ

CANopen to Modbus RTU Gateway. Supports operating temperatures between -25 to 75°C.

Gọi 0904251826 để được trợ giúp

Bộ chuyển đổi CANopen sang Modbus RTU ICP DAS I-7232D

Features

I-7232D applicationThe I-7232D CANopen to Modbus RTU Gateway is an ICP DAS CAN bus product. The device allows a CANopen master to access the Modbus slave devices on some Modbus RTU network. Modbus RTU protocol is a kind of application protocol based on RS485 network. This gateway provides an easy way to connect Modbus RTU devices with CANopen network These Modbus RTU devices may be a PLC, a Modbus RTU sensor, or ICPDAS M-7000 series modules. We also provide the utility software for users to configure the I-7232D,s parameters and build the EDS file for the CANopen master interface. Users can easily apply Modbus RTU devices in CANopen applications wit the I-7232D.

  • NMT: Slave

  • Error Control: Node Guarding protocol

  • Node ID: Setting by CAN_MRU Utility Software

  • PDO Modes: Event-triggered, remotely requested, cyclic and acyclic SYNC

  • PDO Mapping: variable

  • No of SDOs: 1 server, 0 client

  • Emergency Message: Yes

  • CANopen Version: DS-301 v4.01

  • Device Profile: DSP-401 v2.0

  • CAN Baud Rate setting by utility:

    • 10K, 20K, 50K, 125K, 250K, 500K, 800K, 1M bpse

  • Modbus Baud Rate setting by utility:

    • 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 bps

  • RUN, ERR, and OVERRUN LED indicators

  • Support max 10 Modbus RTU I/O series modules

  • Provide friendly Utility for parameters configuration.

  • 7-segmemt LED to show Node ID, CAN baud rate and RS-485 baud rate

Applications:

  • Control Systems

  • Building Automation

  • Factory Automation

  • Distributed Data Acquisition

Utility

The I-7232D Utility helps users to configure the devices, and has following features:

  • Support CANopen node ID, baud rate setting

  • Provide Modbus RTU parameters setting

  • Display Modbus RTU devices configuration

  • Show CANopen application objects configuration

  • Produce EDS file Dynamically

I-7232d_ap2

Usage

The simple steps about how to use CPS_DCON gateway are described as follows:

  1. Select Modbus RTU devices for users' CANopen application

  2. Set the Modbus RTU devices 10 parameters into I-7232D by CAN_MRU Utility

  3. Configure the I-7232D and create EDS file

  4. Apply EDS file to CANopen application

  5. Implement the I-7232D in CANopen network

Usage

Modules Support

Only the following Modbus RTU commands are supported by the gateway.

Code

Name

Description

01

Read Coil Status

Read the ON/OFF status of discrete outputs in the slave

02

Read Input Status

Read the ON/OFF status of discrete inputs in the slave

04

Read Input Registers

Read the binary contents of input registers in the slave

06

Preset Single Register

Preset an integer value into a single register

15

Force Multi Coils

Forces each coil in the sequence of coils to either ON or OFF

Specifications

Model  

I-7232D

 CPU

80188, 40MHz  

 Flash  

512K bytes

 SRAM

    512K bytes    

 EERROM

2K bytes (Can upto 128K bytes or change to 2K/8K FRAM)

 NVRAM

32 bytes

 Real Time Clock

16 bit

 Watch Dog Timer

CPU Built-in

 COM1

RS232: TXD,RXD,RTS,CTS,GND

 COM2

RS485: D2+, D2-

 Communication Speed

117200 max

 CAN Controller

Phillip SJA1000T CAN Controller

 CAN Transceiver

Phillip 82C250/251CAN Transceiver

 LED Directors

ERR, RUN, OVERRUN

Display

7-segment LED: 5digit

 Isolated

2500Vrms on CAN side

 Power Supply

20W unregulated +10VDC to +30Vdc

 Operating Temp

-25C to 75C

 Storage Temp

-30C to 85C

 Humidity

5 ~ 95%

Dimensions

133 x 72 x 33 mm